5.2 Troubleshooting
WARNING - Installation and service should only be performed by a qualified service person and
should conform to all local codes
Verify that the equipment being used
to charge the RMBE is working
properly and is not overcharging or
undercharging the battery set.
External Charger not working
properly
Verify internal batteries are not
damaged and that they are charged -
replace if necessary.
Discharged / Bad Battery
Verify that total output current is less
than rated current of RMBE
Excessive loading on output
Verify proper configuration jumper
setting
Incorrect configuration jumper setting
The battery voltage is incorrect
Verify internal batteries are not
damaged and that they are charged -
replace if necessary.
Discharged / Bad Battery
Ensure that all internal wiring of the
RMBE is connected properly.
Internal wiring disconnected or
connected improperly
See aboveExcessive loading
Verify proper configuration jumper
settings and that there is not an
overcurrent condition, remove output
wiring or voltage selection jumper for
30 seconds, then replace the jumper.
Tripped PTC(s)
Verify that the configuration jumpers
on the back panel are installed
appropriately (See Section 5)
Configuration jumpers missing
No battery voltage present
SolutionPossible CauseCondition