Functions (cont’d)
PRESET DEVIATION ALARMS
The RMB provides two deviation alarms, preset to 30 °F or 17 °C above and
below setpoint value. If the process temperature falls below the setpoint
minus the low deviation alarm value, or if the process temperature rises
above the setpoint plus the high deviation alarm value, the controller enters
the alarm state. The Alarm LED will illuminate. A port line is enabled on the
communications connector strip that can be used to activate the audible
alarm on Athena’s ACM or ASM communications module (or similar
module like the mainframe endplate module) if one is included in the sys-
tem. When a deviation alarm condition occurs, this port is activated.
CURRENT MONITOR / OUTPUT FAILURE DETECTION
The Current Monitor processor continually monitors heater current readings
to ensure that they correlate with output activity.
If the output device signal (HEAT) is off and a current flow is detected, then
the processor will post a triac short error, the lower display will toggle
between “Out” and “SHrt,” and the Alarm LED will illuminate. All other
indicators will be off, and all control processing will terminate.
If the output device is on but no current flow is detected, then the processor
will post a bad heater error, the lower display will toggle between “bAd” and
“Htr,” and the Alarm LED will illuminate. All other indicators will be off, and all
control processing will terminate.
If either of these error conditions is detected, and the Power Interrupt option
is installed, a relay will open to shut off power between the triac and heater.
There is no automatic recovery from either of these error conditions. Once
detected and posted, power to the unit must be reset for control processing
to resume.
SENSOR ERROR DETECTION
When a sensor error is detected, the upper display will alternately flash
between “TC” and the cause of the thermocouple error. “rEv” occurs if the
thermocouple is reversed, and “oPn” occurs if the thermocouple is open. The
alarm LED will illuminate, and the output will be disabled. When “rEv” or
“oPn” occur, the unit goes into Manual Mode 0%.
NORMAL OPERATING MODE DISPLAY FUNCTIONS
In the absence of any special circumstances or error conditions, the upper
display (3-character display) of the RMB is dedicated to the presentation of
the Process Value when the unit is in Normal Operating MODE. The
Process Value is displayed in accordance with the temperature scale
established by the “Units” jumper.
In the absence of any error conditions, the lower display (4 character
display) of the RMB is used to present a variety of items. The operator can
index through the available items with brief presses of the DISPLAY key.
AUTOTUNE ACTIVE INDICATION
Whenever the Autotune Process is active, the upper display will alternately
flash between Autotune (tUn) and Process Value.
The Autotune process will terminate when completed, or when an error has
been detected. When autotuning is completed, the flashing Autotune Active
display (tUn) will revert to a steady display of the process value. When the
process self-terminates due to an error condition, the Autotune Active
display will flash alternately with an error code, indicating the specific error
condition that has occurred. (see page 16).
The Autotune process can also be terminated by pressing the Mode key
while the Autotune process is active. The unit will revert to auto control
mode, and the flashing Autotune Active display will be replaced with a
steady readout of the process value.